So, you’ve just received your remanufactured Fisher® DVC6200 controller. What’s next?
The first thing you need to do is calibrate the device following the instructions below. If you have any questions or run into any problems, call (800) 325-4808 to speak with one of our product technicians.
Click here to download a one-page, easily printable version of these instructions.
Steps to Calibrate a DVC6200 Controller
On receiving a DVC6200 the instrument mode is “In Service.” Follow these simple steps to get your device up and running.
- Hook up a HART® communicator to the DVC6200 in parallel with a 4-20 mA loop across the “loop” terminals
- Apply a 4 mA signal to the DVC and power up the HART communicator
- First, put the instrument in “not in service” mode. Do this by entering the menu ‘configure’, then ‘detailed setup’, then ‘mode and protection’, then ‘instrument mode’
- Choose “not in service” and press enter
- Hit the home key to return to the main menu
- Now enter ‘configure’, then ‘guided setup’, then ‘setup wizard’
- Entering ‘setup wizard’ will start you through configuration prompts asking for information about the actuator and valve you are working with
- Enter the actuator manufacturer, type, size, and supply pressure requirements as requested by the communicator
- When asked, go ahead and send the factory defaults to begin with (fine tuning can be adjusted later)
- After completing the setup wizard portion, the communicator will prompt you to start the auto-travel calibration portion
- When asked for adjustment method for output bias choose manual
- The communicator will automatically stroke the valve to 100% travel and 0% travel and adjust the output bias
- When it asks for 50%, adjust the mA input to 12 mA and proceed with the remainder of the auto-travel calibration procedure
- Afterwards the communicator will prompt you to return it to “in service” mode; do so
- Stroke the valve completely and make sure your valve opens linear to your 4-20 mA input signal
NOTE: Different device descriptions and DVC styles may have slightly different terminology. Path give is based on 375 or 475 communicator structure.