Fisher® EZ Control Valve E-body Actuator Orientation Video

Video: Fisher® EZ Control Valve E-body Actuator Orientation

Fisher 667 & 657 E-body Sliding Stem Globe Control Valves

Fisher® EZ Control Valve Actuator Help

Watch this video for step-by-step instructions to adjust E-body actuator orientation for a remanufactured Fisher 667 or 657 E-body sliding stem globe control valve.

Without following the proper procedure to change the orientation, it’s possible to end up damaging the seat and the plug. In this video we will demonstrate how to adjust E-body actuator orientation without damaging your valve.

667 Air to Open Actuator:

  1. Raise the valve plug off the seat by applying air to the actuator
  2. Loosen up the Yoke Nut and turn the whole actuator 180 degrees
  3. Tighten back up the Yoke Nut
  4. Release the air to bring your valve plug back down to the seat

For a 657 Air to Close actuator, with air pressure released from the actuator, all you have to do is loosen up the Yoke Nut and turn it. Then tighten the Yoke Nut down again.

If you have any questions, please give us a call at 800-325-4808. And don’t forget to check back on our website and social media channels for future Two Cent Tech Tips!

Browse our Ultimate Cheat Sheet on Fisher® Control Valves to learn more about remanufactured control valves.

Need More Information?

Please fill out the form below and an Automation Service representative will contact you shortly. All fields are mandatory unless labeled optional.

  • We take your privacy seriously. No spam.
    By submitting this form I agree to be contacted by Automation Service via email or phone if provided. See our Terms and Privacy Policy.
  • This field is for validation purposes and should be left unchanged.